Connections to Guardall (DIGI) with the Webway DCM
RX16i, QX32i, PX48i and PX80i includes an integrated dialler
PX500 and PX250HS does not include an integrated dialler – an external one is required on the panel
QX18i and QX34i includes an integrated dialler
QX18 and QX34 does not include an integrated dialler – an external one is required on the panel
PX18, PX34 and PX80 does not include an integrated dialler – an external one is required on the panel
Digital communicator connection
Connect the A and B ‘PSTN’ terminals and ground on the WebWay to the A and B telephone connections on the
Guardall alarm panel.
Connect the WebWay PWR + and - to any relevant Power and Ground terminals.
Guardall alarm panel configuration for all ranges
Select menu 11 telephone number 1
Select Tel Number <1>
Enter Tel Number <01234 567890> (any valid phone number is acceptable)
Select Format <SIA>
Select Module <Int. Dlr.> - this will be Ext. Dlr if an external dialer module was required on the panel
Select Auto Test <Off>
Select Attempt <0>
Select Backup <0>
Select Alarm <On>
Select Set/Unset <On>
Select Bypass <On>
Select Trouble <On>
Select Log On <On>
Select Eng On <On>
Select Reset <On>
Select Restore <On>
Press X button twice
Select menu 12 GSR 1
Select Enable <Auto>
Enter S/N <______> (GSR dongle Serial number)
Enter GSR ID <Communicator Site ID>